ČSN EN 50380 ed. 2

3 Terms and definitions
3.10 electrical characteristics
OCP(MAX) Maximum overcurrent protection rating

3 Terms and definitions
3.11 rated current of overcurrent protection (OCP) device
current rating of fuse or circuit breaker according to EN 60269-6

4.3 Mandatory information
4.3.2 Electrical, including wiring, information
Overcurrent protection devices with a 1hr, 1,35 IR overload rating, where IR is the rated value of the overcurrent protection device, are recommended.

Annex C (informative)
Electrical characteristics for PV power plant design
C.2 Temperature corrections
With the provided temperature coefficients TC electrical parameters y given for a reference temperature TReference can be calculated to other operating temperatures T:
y=yreference[1+TC(TTreference)]